FRP water tank installation instructions

Release Date: January 03, 2018Keyword: FRP Water Tank Install FRP Water Tank
FRP water tank installation instructions
1: Do a good job in the processing of the strip foundation beam, level it so that it is on the same plane, and the error (± 0.5cm)


焊接槽钢: 根据水箱尺寸焊接好槽钢,长宽与水箱底板尺寸一齐,对角测量尺寸误差为±1.5cm 保障焊缝均匀,排缝一齐。 2 : Welded channel steel : Welded channel steel according to the size of the water tank. The length and width are the same as the size of the bottom plate of the water tank. The diagonal measurement has a size error of ± 1.5cm to ensure uniform welding and uniform seams.


安装底板:根据水箱板上的印号和说明,排列,两张单板之间添加密封胶条,螺丝连接连接底板,使其密封牢,螺丝加力时要加力均匀,每个螺栓加力3-4次,不得用力过猛,否则会因用力不均匀造成裂板现象。 3 : Install the bottom plate: arrange according to the number and instructions on the water tank plate. Add sealing strips between the two boards. Screw the connection bottom plate to make it tightly sealed. When the screw is applied, apply even force. Each bolt After 3-4 times, do not use too much force, otherwise it will cause cracking due to uneven force. The bottom plate and the channel steel are connected with a fixed angle iron, so that the water tank body is fixed on the water tank foundation.


4: Installation of side plates: According to the number and description on the single board of the water tank, find the side plates of each layer of the water tank, separate them in advance, and connect the side plates with bolts. Set the water tank plate upright, make the side plate and the bottom plate of the water tank at an angle of 90 °, clamp the sealing tape, and tighten the bolts.


安装内拉筋:根据水箱尺寸,找对拉筋的数量和长度。 5 : Installation of internal ribs: According to the size of the water tank, find the number and length of the ribs. Use the rib plate to measure the tightening point of the wire to the wire, draw marks, punch holes, and tighten the wire, so that the wire is flat and balanced with the water tank. If there is a large error between the box and the ribs, you can adjust the error by adjusting the bolt tightening degree until the error is adjusted to a small level.










6: Cover plate installation: install the top plate of the water tank, tighten the bolts evenly, and do not use too much or too little force. After adjusting the water tank fasteners, determine the position of the openings according to the site requirements, open the water inlets and outlets, and install the flanges to connect the valves.


The installation is complete